ECN-R

Dual Element, Time-Delay Fuse
* ECN-R replaces HAC-R
Volts:                          250Vac (or less), 125Vdc
Amps:                         1-600A
IR:                               200kA RMS Sym
Agency Information:    CE, Std. 248-12, Class RK5, UL Listed, Guide JDDZ, File E162363, CSA Certified, C22.2                                                       No. 248.12, Class 1422-02, File 700489
Typical Applications:    AC power distribution system mains, feeders, and branch circuits • Protection of motors and motor                                       branch circuits • Protection of transformers and other inductive loads • All general-purpose                                                   applications including lighting, heating and other non-inductive loads

Features:
• True dual-element construction allows sizing of 125% FLA for motor backup protection
• Superior overload and cycling capabilities
• Current limiting provides component short-circuit protection

Product Details

Catalog Number Description Case Quantity
ECN-R-5 250V Dual Element Time Delay 5A 10
ECN-R-10 250V Dual Element Time Delay 10A 10
ECN-R-15 250V Dual Element Time Delay 15A 10
ECN-R-20 250V Dual Element Time Delay 20A 10
ECN-R-25 250V Dual Element Time Delay 25A 10
ECN-R-30 250V Dual Element Time Delay 30A 10